BUILT IN THE USA. READY FOR YOUR PROJECT.
Electrical Switchboards for Oil and Gas
Oil and gas facilities depend on reliable distribution to pumps, compressors, process controls and support equipment, often under demanding site conditions.
DIRECT FROM THE MANUFACTURER / NEW EQUIPMENT

THE MANUFACTURER’S PERSPECTIVE — 02
Oil and gas facilities depend on reliable distribution to pumps, compressors, process controls and support equipment, often under demanding site conditions. A new low-voltage switchboard should be specified around those loads and their operating environment, not selected by current rating alone. For owners and engineers, the key purchasing task is to define the electrical duty, installation boundary and documentation before comparing proposals.
Start with the process and feeder schedule
Provide an updated one-line showing every source, transformer, main device and outgoing feeder, together with system voltage, phases, grounding and the available fault-current data. A load schedule should distinguish running demand from intermittent or standby equipment and identify future additions. The engineer can then assess bus capacity and the actual number and arrangement of feeder positions.
Motor-driven pumps and compressors create different demands during starting and normal operation. Supply motor ratings, starting methods, expected duty and any drive information so the design team can evaluate voltage drop and feeder protection. A switchboard distributes power to motor control centers or drives; it should not be assumed to provide all motor-control functions itself.
Place the assembly around the site classification
The owner's area-classification drawings should identify whether the proposed installation is in an unclassified or classified location, including the applicable gas or vapor conditions. Locating a switchboard in a suitably designed electrical building outside a classified area may simplify equipment selection, but it introduces building, cable-route and ventilation interfaces that require early coordination.
If the intended location is classified, the engineer and authority having jurisdiction must evaluate the complete installation and the suitability of the proposed equipment and protective measures. A weather-resistant enclosure alone does not establish suitability for a hazardous location. Include the classification basis and any building pressurization or monitoring requirements in the request for review.
Balance protection with process continuity
Submit utility or upstream source fault contribution, transformer impedance and the operating configurations that can change fault duty. The engineer must compare those conditions with the proposed assembly and device ratings, including interrupting capability and applicable short-circuit withstand. A rating on one breaker is not, by itself, proof that the entire switchboard is suitable.
Ask the protection-study provider to assess feeder and upstream device coordination across relevant fault levels. Keeping a faulted pump feeder from unnecessarily interrupting an adjacent process may influence trip-unit selection and settings. Coordination, clearing time and arc-flash risk can pull in different directions, so the owner should approve the operating priorities and review documented study results.
Design for exposure and operator access
Describe outdoor or indoor placement, ambient conditions, dust, moisture, corrosive contaminants and washdown exposure. The enclosure, finish, ventilation and condensation-control strategy should be selected together: sealing against contaminants may complicate heat removal. Provide the room ventilation designer with expected equipment heat rejection and confirm that the equipment's ratings remain appropriate for the specified environment.
Review footprint drawings for cable entry, bend space, lifting routes and access to devices, terminations and meters. Site layout must accommodate applicable working clearances and the manufacturer's service requirements. Consider whether operators need status indication at a different location and whether planned maintenance will affect neighboring feeders; extra access or separation can increase lineup size and cost.
Define controls, metering and source interfaces
For a switchboard feeding a process-control system, agree on the signals exchanged: breaker status, trip indications, alarms, metering values and any authorized remote commands. Identify communication protocol, control-power source, terminal locations and the party responsible for network integration. A point list and interface drawing make the boundary between the assembly and the site control system testable.
Where a generator or alternate source is involved, document source capacity, transfer equipment, interlocks and the intended operating states. Confirm which party supplies transfer logic and which protection study covers each source configuration. Emergency shutdown functions should be assigned explicitly to the appropriate safety system; a general distribution alarm or remote command should not be treated as a substitute.
Purchase with clear deliverables and milestones
Request proposals for a newly manufactured assembly using the same one-line, environmental criteria, device schedule and delivery constraints. Compare inclusions and exceptions for metering, spare feeder provisions, documentation and factory testing, not just the quoted equipment scope. Where UL 891 is specified for an appropriate switchboard, verify the proposed assembly's project-specific listing and scope before approval.
Set review milestones for drawings, component approval, fabrication, factory checks and shipment; unresolved interfaces or component changes can affect the schedule. Specify test records, final drawings and operating manuals for turnover, and identify responsibility for rigging, field connections, studies and commissioning. Installation, testing and energization belong to qualified personnel working under site procedures, applicable codes and manufacturer instructions.
LET'S BUILD SOMETHING RELIABLE — 03
Ready to talk
switchgear?
Tell us about the new equipment your project needs. Include as much or as little detail as you have today.
(951) 403-5738CALL TO DISCUSS YOUR PROJECT